HP Series Pure Sine Wave Inverter 
HP-PV Series Pure Sine Wave Inverter is a combination of an inverter, solar power and Auto-transfer switch into one complete system . It is packed with unique features and it is one of the most advanced inverter/chargers in the market today.

Electrical Specifications
Inverter Output Model 1KVA 1.5 KVA 2KVA 3.KVA 4KVA 5KVA 6KVA 7.5KVA 10KVA 15KVA
Continuous Output Power 1KW 1.5 KW 2KW 3KW 4KW 5KW 6KW 8KW 10KW 12KW
Surge Rating (20Secs) 3KW 4.5 KW 6KW 9KW 12KW 15KW 18KW 24KW 30KW 36KW
Output Waveform Pure Sine wave/Same as input(Bypass Mode)
Nominal Efficiency >88%(Peak)
Line Mode Efficiency >95%
Power Factor 0.9-1.0
Nominal Output Voltage rms 100-110-120Vac / 220-230-240Vac
Output Voltage Regulation ±10% RMS
Output Frequency 50Hz ± 0.3Hz/60Hz ± 0.3Hz
Short Circuit Protection Yes( 1sec after fault )
Typical transfer Time 10ms(Max)
THD < 10%
DC Input Nominal Input Voltage 12.0Vdc/24.0Vdc/48.0Vdc 24.0Vdc/ 48.0Vdc 48.0Vdc
Minimum Start Voltage 10.0Vdc/ 10.5Vdc for 12Vdc Mode  *2 for 24Vdc,  *4 for 48Vdc ;
Low Battery Alarm 10.5Vdc/ 11.0Vdc for 12Vdc Mode
Low Battery Trip 10.0Vdc/ 10.5Vdc for 12Vdc Mode
High Voltage Alarm 16.0Vdc for 12Vdc Mode
Low Battery Voltage Recover 15.5Vdc for 12Vdc Mode
Idle Consumption-Search Mode < 25 W when Power Saver On.
Charger Output Voltage Depends on battery type
Charger Breaker Rating 20A 20A 20A 25A 32A 40A 40A 50A 80A 80A
Max Charge  Power Rate 1/3 Rating Power
Battery Initial Voltage for Start 10-15.7Vdc for 12Vdc Mode *2 for 24Vdc,  *4 for 48Vdc ;
Over Charge Protection Shutdown 15.7Vdc for 12Vdc Mode
BTS Battery Temperature Sensor (Optional)  YesVariances in Charging Voltage & S.D Voltage Based on the Battery Temperature.
Bypass & Protection Input Voltage Waveform Sine wave (Grid or Generator)
Nominal Voltage 100-110-120Vac / 220-230-240Vac
Max Input AC Voltage 150VAC For 120Vac LV Mode;  300VAC For 230Vac HV Mode;
Nominal Input Frequency 50Hz or 60Hz (Auto detect)
Low Freq Trip 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz
High Freq Trip 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz
Overload protection (SMPS load) Circuit Breaker
Output Short circuit protection Circuit Breaker
Bypass Breaker Rating 20A 20A 20A 25A 32A 40A 40A 50A 80A 80A
Transfer switch Rating 30Amp for UL & TUV 40Amp for UL 80Amp for UL
Bypass Without Battery Connected Yes (Optional)
Max Bypass Current 30Amp 40Amp 80Amp
Solar Charger (Optional) Rated Voltage 12Vdc / 24Vdc / 48Vdc
Solar Input Voltage Range 15-45Vdc / 30-70Vdc / 60-100Vdc
Rated Charge Current 40 or 60A
Rated Output Current 15A
Self Consumption < 10mA
Bulk Charge (Default) 14.5Vdc for 12Vdc Mode *2 for 24Vdc, *4 for 48Vdc
Floating Charge(Default) 13.5Vdc for 12Vdc Mode
Equalization Charge(Default) 14.0Vdc for 12Vdc Mode
Over Charge Disconnection 14.8Vdc for 12Vdc Mode
Over Charge Recovery 13.6Vdc for 12Vdc Mode
Over Discharge Disconnection 10.8Vdc for 12Vdc Mode
Over Discharge Reconnection 12.3Vdc for 12Vdc Mode
Temperature Compensation   -13.2mV/°C for 12Vdc Mode
Ambient Temperature 0 ~ 40°C(Full load)  40 ~ 60°C(Derating)
Mechanical Speccifications Mounting Wall Mount
Inverter Dimensions (L*W*H) 388*415*200mm 488*415*200mm 588*415*200mm
Inverter Weight (Solar Chg) KG 21 +2.5 22 +2.5 23 +2.5 27 +2.5 38 +2.5 48 +2.5 49 +2.5 60 +2.5 66 +2.5 70 +2.5
Shipping Dimensions (L*W*H) 550*520*310mm 650*520*310mm 750*520*310mm
Shipping Weight (Solar Chg)KG 23 +2.5 24 +2.5 25 +2.5 29 +2.5 40 +2.5 50 +2.5 51 +2.5 62 +2.5 68 +2.5 72 +2.5
Display Status LEDs / Status LEDs+LCD
Standard Warranty 1 Year